Dehumidification Calculator
Psychrometric properties from the ASHRAE Handbook — Fundamentals (Hyland–Wexler saturation pressure); the air-VPD is the saturation deficit of the air itself, leaf VPD is higher when leaves are warmer.
This is only the water held in the air. In a growing room the continuous load from plants (card 3) is usually far larger than this one-off amount.
1 room air · ADP coil surface · 2 air leaving the coil · 3 air leaving the unit · ◯ target state. The coil process follows the straight line from 1 towards ADP; the condenser reheats at constant humidity ratio.
The air is treated as a mixture of dry air and water vapour. The refrigerant coil is modelled with the apparatus dew point (ADP) and a bypass factor, as in cooling-coil selection: a share BF of the air bypasses the coil, the rest leaves saturated at the ADP. Latent heat of the condensed water and the compressor work are both rejected by the condenser back into the same air stream, which is why a dehumidifier warms the room.
- 0.68 kWh per litre is the latent heat that must be pulled out of the air (≈ 2.45 MJ·kg⁻¹). A heat pump moves it with COP × less electricity, so the ceiling is about 1.47 × COP L·kWh⁻¹; real units land at 40–70% of that because they also cool the air sensibly and run a fan.
- Portable units: ENERGY STAR integrated energy factor ≥ 1.77 L·kWh⁻¹ (50-pint class), best models ≈ 2.5; whole-house units ≥ 1.30. Rated at 18 °C / 60% RH under the 2019 US DOE procedure (older labels used 27 °C / 60% or 30 °C / 80%, which inflates capacity). Expect roughly half the label capacity at 20 °C / 60% RH.
- Greenhouse heat-pump dehumidifiers that recirculate warm room air reach ≈ 4 L·kWh⁻¹ (e.g. 48 L·h⁻¹ units) — the reference class for controlled-environment agriculture.
- Condensation needs a cold coil: the room dew point must be above the ADP. Below about 15 °C and 45% RH a refrigerant unit loses most of its capacity and a desiccant wheel is preferred; the coil must stay above 0 °C or it frosts.
- Plants return ≈ 95% of the water they take up to the air. Lettuce transpires 4–6 L per m² of leaf area per day; per m² of growing area in a vertical farm plan on 1.5–3 L·d⁻¹ (≈ 100 g·m⁻²·h⁻¹ under lights) and up to three quarters of it can be recovered as irrigation water.
- Size for the peak (lights on, canopy closed) and let the unit cycle; add 20–30% margin for sensor and control lag. Ventilating with outdoor air only helps when the outdoor humidity ratio is lower than indoors — compare g·kg⁻¹, not % RH.
Sources: ENERGY STAR dehumidifier criteria, ENERGY STAR test conditions, DryGair DG12 data, Water use efficiency in vertical farming (Agric. Water Manag., 2023), Vertical farming review (Agron. Sustain. Dev., 2025), ASHRAE Handbook — Fundamentals, ch. 1 (Psychrometrics).